The earth tester enables you to perform the following operations:
- Checks the resistance of the earth socket in the range of 0 – 2000?
- Locates the position of the live pin (right or left), check the earth connection.
- Checks for 230V (or an abnormal voltage)
- Checks continuity (earth conductor, main and local equipotential connections)
These test points are required by standard NF C 15-100 and assist in delivering a compliant installation.
To facilitate testing, the tester can be used directly on 2P+E 10/16 A sockets.
In addition, the two-color backlighting will alert you instantaneously to the condition of your installation.
Blue: OK, Red: fault (earth>100Ω, incorrect voltage, etc.)
Confirms to IEC 61010-1 EN 612557-4
Installation Category III
Class II IP-40, IK06
Principle of measurement by “fault loop” for installations with neutral as per diagram TT
Earth loop measurement current less than the drop-out threshold of the 30mA circuit breakers
Measurement of the earth resistance by 31 / 2 digit display from 0 to 1999Ω (resolution 1Ω, measurement updated every 1.5s)
Accuracy | +/- (3% + 3digit) for pure resistance (range 0-200Ω at 23°C +/- 5°C) |
Operating voltage | 230V (Ph/N) -10/+6% |
Operating frequency | 50/60Hz |
IEC 61010-1 EN 61557-4 | |
Installation category III | |
Class II IP40,IK06 | |
Operating temperature | -15°C /+45°C |
Storage temperature | -25°C /+70°C |
Weight | 340g (unit alone) |
Dimensions of unit | W=72mm L=210mm H=50mm |
Two-colour back-lit LCD display |