Leakage Current Clamp Meter


AC Leakage Current Clamp With High Current Measurement Up To 1000A

DT-9812

Identifying deterioration of installation and other causes of "nuisance tripping" in live circuits is not always a straightforward matter. Problem of access and isolation may make the inspection costly. Then, lets look at CEM Leakage Clamp Meter designed to take the stress out of inspecting live installations.

Now, thanks to unique AC Leakage Clamp Meters developed by CEM, we can make not only a precise measurement of the earth leakage current in a circuit, but also an instant assessment of the cause of that leakage without shutting down the installation.

At the first glance, the CEM Leakage Clamp meters appear to be conventional clamp ammeters. However, the special construction of the clamp shielding, allows us to measure tiny out- of-balance currents between any conductors enclosed within the transformer jaws. 

add to enquiry Download PDF

 

  • Accurate AC digital clamp meter for leakage current measurement
  • 100uA high resolution on 200mA range
  • Shield transformer jaws to minimizes the effect of external stray magnetic field
  • Large jaw with 68 mm diameter
  • Five Ranges (200mA, 2A, 20A, 200A, 1000A) for all application.
  • A filter circuit is designed to eliminate the effect of high frequency noise and harmonics by setting the frequency selector switch at the 50/60 Hz position for AC current measurement
  • Large 3 - 1/2 digits backlit LCD
  • Fast bargraph display (20 times/sec.) for transient observation
  • Continuity Test
  • Max/Min record function
  • Peak Value Measurement
  • 600V overload protection for DC/ACV, ohm range measurement
  • Easy single rotary switch for any function selection
  • Data Hold Function

 

General Specifications

Conductor Size 68 mm max. (approx. )
Battery Type One 9V NEDA 1604
Display MAX. 6000 counts  LCD with 32seg. Bargraph
Range Selection Manual
Overload Indication Left most digit blinks
Max/Min Records Maximum and Minimum values
Data Hold  Freezes Displayed Data
Power Consumption 10 mA (approx. )
Sampling Time 2  times/sec.(display )
20  times/sec.(bargraph )
Operating Temperature -10 °C to 50°C
Operating Humidity less than 85% relative
Storage Temperature -20 °C to 60°C less than 75% relative
Storage Humidity less than 75% relative

 

 

 

Eloectrical Specifications 

 

AC Current

    Accuracy 
Range Resolution  50/60 Hz  Wide (40-1KHz) 
200mA  100uA  ±1.5% ± 6dgts  ±3.0% ± 6dgts 
2A  1mA  ±2.0% ± 6dgts  ±4.0% ± 6dgts 
20A  10mA  ±2.0% ± 6dgts  ±4.0% ± 6dgts 
200A 100mA  ±2.0% ± 6dgts  ±3.0% ± 6dgts 
1000A 100mA  ±3.0% ± 6dgts  ±7.0% ± 6dgts 

 

 AC/DC Voltage( input impedance:10MΩ)

Range Resolution Accuracy Overload protection
50/60Hz 40-1KHz
600V 0.1V ±1.5%±2dgts ±2.0%±4dgts AC/DC 600V

 

Resistance 

Range Resolution Accuracy Beeping OL Protection
0.4-400Ω 0.1Ω ±1.5%±4dgts <38.0Ω AC/DC 600V

 

 